KILL_NANCY Publish time 27-4-2018 04:00 AM

[BASIC]How To Calculate 33/11 KV Carry Line

Edited by KILL_NANCY at 27-4-2018 04:02 AM

CALCULATION 33KV / 11KV CARRY LINE                               

If details are :                                                                
                                                               
V         : 415                                                       
PF         : 0.9                                                       
CT KVA        : 1000                                                       
                                                               
FORMULAE       
                                                               
KW : KVA X PF                                                               
KW : 1000 X 0.9                                                               
KW : 900                                                               
                                                               
11KV PRIMARY CURRENT                                       
                                                               
KW : Root (3) X KV X I X PF                                                               
900 : 1.732 X 11 X I X 0.9                                                               
900 : 17.1468 X I                                                               
900/17.1468 : I                                                               
52.49       : I                                                       
I       : 52.49A                       
                                                               
415V SECONDARY CURRENT                                       
                                                               
WATTS : Root (3) X V X I X PF                                                               
900 X 1000 : 1.732 X 415 X I X 0.9                                                               
900000       : 646.90 X I                                                       
900000/646.9 : I               
1391.3       : I                                                       
I       : 1391.3A       
                                                               
RATING OF TRANSFORMER 1000 KVA                                       
                                                               
        Primary Voltages on High Voltages sided is : 11KV                                                       
        Primary Current on High Voltage i : 52.49A
                                                               
        Secondary Voltages on Low Voltages sided is : 415V                                                       
        Secondary Current on Low Voltage is : 1391.3A       
                                                               
        Transformer rating in KVA : 1000KVA                                                       
        Primary Voltages : 11KV                                                       
        Primary Current : 52.49A                                                       
        Secondary Voltages : 415V                                                       
        Secondary Current : 1391.3A                                                       
                                                                CALCULATION FOR THE RATING OF TRANSFORMER ACCORDING TO :                                                       
                                                               
        P : V X I (Primary Voltage X Primary Current)                                                       
        P : 11000V X 52.49A = 577390VA = 577.39KVA                                                       
                                                               
AND                                               
                                                               
        P : V X I (Secondary Voltage X Secondary Current)                                                       
        P : 415V X 1391.3A = 577390VA = 577.39KVA                                                       
                                                               
        P : Root (3) X V X I                                                       
        P : Root (3) X Primary Voltage X Primary Current                                                       
        P : 1.732 X 11000V X 52.49A = 1000039.48VA = 1000 KVA                
                                                               
        P : Root (3) X Secondary Voltage X Secondary Current                                                        
        P : 1.732 X 415V X 1391.3A = 1000038.6VA = 1000 KVA
                                                               
RATING OF THE THREE PHASE TRANSFORMER                                       
                                                               
        Voltage (line to line)                         : 208V                               
        Current (line current)                         : 1391.3A                               
                                                               
        P : Root (3) X V X I                                                       
        P : 1.732 X 208V X1391.3A                                                       
        P : 501224.2VA                                                       
        P : 501 KVA / 500 KVA                                                       

ABBREVIATIONS               
                                                               
PF         : Power Factor                                                       
I         : Amperage                                                       
KV         : Kilo Volt                                                       
KW         : Kilo Watt                                                       
V         : Volt                                                       
KVA : Kilo Volt Ampere                                                       
CT       : Current Transformer                                                       
P         : Power                                                       
VA       : Voltage Ampere                                       